← Back to Standards Library
IEC 61000-3-2:2018
Electromagnetic compatibility - Limits - Limits for harmonic current emissions (≤16 A per phase)
📅 Issue date:—
🔄 Effective date:—
🌍 Type:International standard
01 Scope
Specifies limits for harmonic currents injected into the public low-voltage supply by equipment with input current ≤16 A per phase, managed by class A/B/C/D.
03 Terms and definitions
Performance criteriaA/B/C by degree of functional preservation.
04 Technical requirements
2nd 1.08 A, 3rd 2.30 A, 5th 1.14 A, 7th 0.77 A, etc. (2~16 A input).
Expressed as % of fundamental, e.g. 3rd ≤30%×λ.
IT equipment with specified waveform, ≤600 W, in mA/W.
Disclaimer:This page is a technical summary of the corresponding standard for quick reference. All limits, clauses and methods are subject to the official publication and its latest amendments; formal compliance assessment must refer to the official issued text.